Normal |
Normal |
Mild temperature at vents |
Excessive system oil level |
Drain the climate control system. Clean the entire system, removing oil and residues, then recharge it. |
|
Air/moisture in the system |
|
High |
High |
Low pressure pipe colder than the evaporator |
Expansion valve too open |
Replace the expansion valve Op. 5040B30 EXPANSION VALVE (ORIFICE TUBE) - R+R |
|
Check if the high pressure drops by pouring water on the condenser |
1) Excessive system coolant. 2) Condenser fan faulty 3) Condenser blocked |
1) Drain the system and recharge it 2) Check/replace the condenser fan 3) Clean the condenser |
|
High and low pressure reach the same value as soon as the compressor deactivates and both vary when the compressor is operating |
1) Exhaust valve faulty 2) Gaskets faulty |
Replace the compressor Op. 5040A20 AIR CONDITIONING COMPRESSOR - R.R. INCLUDES CHECKING FLUID LEVEL AND TOPPING UP IF NECESSARY |
|
Low |
Low |
Mild temperature at vents |
Low level of coolant gas in the system caused by the presence of leaks |
Restore the correct operation, then drain the system and recharge it. |
|
Low pressure pipe and pipe end are colder than the evaporator. |
Obstructions on the low pressure side |
Repair/replace the pipes |
|
High |
Low |
Ice on pipes |
Obstructions in the air conditioning system |
Restore correct operation |
|
Ice on evaporator |
Evaporator blocked |
Replace the evaporator Op. 5040C64 A/C EVAPORATOR - R+R |